What the transformer's own impedance spends under load.
The drop is worked by the standard regulation approximation. The percent impedance divides into its resistance and reactance parts through the X/R ratio — %R = %Z ÷ √(1 + (X/R)²) and %X = %R × (X/R) — and at a load fraction β (load ÷ rating) and lagging power factor cos φ, the drop is %Vd = β × (%R cos φ + %X sin φ), with sin φ = √(1 − cos² φ). The figure is the approximation at the stated load and power factor; the exact regulation also carries the second-order term in (%X cos φ − %R sin φ), small at distribution impedances. A leading power factor reverses the sign of the sin φ term and can raise the secondary voltage instead of dropping it — this calculator works the lagging case, the usual one. On-load tap changers correct the ratio itself and are a separate adjustment.