Voltage Drop — Circuits

What the run itself spends, and what the load has left.

volts
amperes
feet
—

The drop is worked by the standard circular-mil method: Vd = 2 × K × I × L ÷ CM single-phase, and √3 × K × I × L ÷ CM three-phase, where L is the one-way length of the run in feet and CM is the conductor’s area in circular mils (NEC Chapter 9, Table 8). K is the conductor’s resistance in ohms per circular-mil foot at 75 °C — 12.9 for copper, 21.2 for aluminum. The method uses that 75 °C resistance; a full AC treatment works from impedance instead and takes the load’s power factor and the raceway material into account, which is a refinement beyond this figure. The percentages are read against the NEC’s informational recommendation — 3% for a branch circuit and 5% for feeder and branch circuit together (the informational notes to 210.19 and 215.2) — which is a recommendation for efficiency of operation, not a requirement of the Code.