Voltage Drop — Transformer Scale

The drop at the transformer's scale: what the impedance spends, on both sides of the ratio, from the power class down to the control transformer.

kVA
percent
volts
percent
kW
kW
kVA
cos φ
—

Regulation is worked from the production readings: %Z from the nameplate or from the short-circuit test voltage, %R from the nameplate or from the load loss at rated current (stated at the 75 °C reference standing), and %X derived as √(%Z² − %R²). The regulation relation carries its first-order term and its second-order term separately, each at its own size, reckoned on the rated secondary voltage; at a leading power factor it can stand negative — a rise, stated as a rise. The runs on both sides are worked by the impedance method of NEC Chapter 9, Table 9, exactly as in the Voltage Drop — Distance tool, in copper and aluminum — the Code’s tables carry no silver or gold standings, and none are filled in. Silver and gold stand in the Materials mode, where the winding and bus resistance is derived from each material’s own resistivity, temperature coefficient, and conductivity standings. Rectifier figures are gross and net in the open: the two conducting diodes’ forward drop is subtracted as its own line, never hidden inside the factor. The energy source named at the head is a standing of the chain, stated beside the result; it changes no figure except where the inverter is the seat. Each run also names its conduit type and its insulation type: the conduit carries its Chapter 9 Table 9 reactance class (magnetic steel, or nonmagnetic), and the insulation carries its Table 310.15(B)(16) ampacity column and the 110.14(C) termination cap, stated as a constraint beside the chain result — for NM-B (Romex), ampacity on the 60 °C basis of NEC 334.80, and for UF-B on the basis of 340.80, stated in words beside their results. Every abbreviation and material used in the options is defined in the reference section below the keypad. The primary and secondary voltages are chosen from the standard ladder defined there — nameplate standards presented as choices, not figures to type: a transformer is built to its rated voltages, where the measured quantities in this tool (the load carried, the test voltage, the losses) are entered as figures, the way a meter or a test set reads them.

Definitions — the run options, the sizes, and the materials

Every option above is defined here at its seat: what the letters stand for, what the thing is, and what its standing governs in this tool — the reactance class a conduit carries into the run's Table 9 figures, the ampacity column an insulation answers to, the temperature basis it stands on.

Conduit and raceway types — each governs the run's reactance class

    Insulation types — the letter system first, then each type

    The insulation letters are the Code's own system (NEC Table 310.4(A) and the type articles): T = thermoplastic; H = heat-resistant (75 °C); HH = high heat (90 °C); W = rated for wet locations; N = nylon outer jacket; X = cross-linked polymer (a thermoset); R = rubber (a thermoset); U = underground / service-entrance use; a -2 suffix = the 90 °C dry-and-wet revision of the base type. Read by its letters, each type name states its own standings — that is how the inference communicates.

      Standard voltages — the ladder both voltage fields present

      The primary and secondary voltage fields present this ladder as choices, and are not typed into. A transformer's voltages are nameplate standards — the ratings the unit is built to — not readings: no meter measures a transformer's rated voltage into being. So the voltages are selected, as a nameplate states them, where the measured quantities in this tool (the load carried, the short-circuit test voltage, the losses, the resistances of the rise reading) are entered as figures, as a meter or a test set reads them. The ladder runs from the utilization voltages at its low end to the distribution-class primaries above 600 V; the wye line-to-neutral partners stand in the same list as their line-to-line voltages, so the list itself shows the √3 relation of §2.2 — 208 with 120, 480 with 277, 4,160 with 2,400, 12,470 with 7,200.

        Sizes

        AWG — American Wire Gauge: the gauge scale of the smaller conductors, 14 AWG through 4/0 AWG; the number falls as the conductor grows. kcmil — thousand circular mils: the size unit of the larger conductors, 250 through 2000 kcmil. Circular mil: the area of a circle one mil (0.001 in) across; a round conductor's area in circular mils is its diameter in mils, squared — the area that stands in the denominator of every resistance figure in this tool.

        Materials

        Conductor materials. Copper — the reference conductor, 100% IACS by definition; the Code's tables carry its standings entire, and it governs the runs and the windings alike. Aluminum — the second Code standing, about 61% IACS; a larger area carries the same conductance. Silver — the highest conductivity of the four (about 108% IACS from its pure-metal resistivity), a laboratory and specialized standing; the NEC tables carry no silver standing, and none is filled. Gold — about 71% IACS, laboratory and specialized, its standing its corrosion-proofness rather than its conductance; likewise no NEC standing. Raceway materials. Steel — magnetic: it concentrates the alternating field, raising the run's reactance and, at the larger sizes, its AC resistance; Table 9's steel class. Aluminum as a raceway — a nonmagnetic metal: Table 9 gives it the same reactance standing as PVC. PVC — polyvinyl chloride, a nonmagnetic polymer: the nonmagnetic class, with ENT (electrical nonmetallic tubing).

        For the figures: select a field, then tap the keys — or type as usual.