Distance is the variable: what the run spends as it lengthens, the gauge the distance requires, and the current it can carry.
The AC drop is worked by the impedance method of NEC Chapter 9, Table 9: Zeff = R · cosφ + X · sinφ (minus for a leading power factor), with R corrected from the table’s 75 °C to the conductor’s operating temperature — the enclosure temperature where one is entered, the ambient otherwise — and X taken at the standing of the conduit type chosen, each conduit carrying its Table 9 class as defined below. DC circuits work from Table 8 resistance, corrected the same way. The circular-mil figure stands beside the impedance figure as its own method: the K-form at 75 °C (K = 12.9 copper, 21.2 aluminum, the NEC standings; K = 11.56 silver, 17.42 gold, computed from resistivity as below), the resistance-only standing. Ampacity is checked under NEC Table 310.15(B)(16) with the ambient correction of Table 310.15(B)(2)(a), the conductor-count adjustment of Table 310.15(C)(1), and the termination cap of 110.14(C) — stated as a constraint beside the result, never merged into the drop. The 3% branch-circuit and 5% combined figures are the NEC’s informational recommendation (the notes to 210.19 and 215.2), a recommendation for efficiency of operation, not a requirement of the Code. Conductor data for copper and aluminum stands as the NEC tables publish it; where a manufacturer’s published figure differs from the Code’s, both stand — manufacturer tables are named as a constituency in this tool’s specification and are not carried as computed data in this build. Silver and gold stand in the material list for laboratory and specialized cases: the NEC tables carry no resistance or ampacity standings for them, so their resistance is computed from resistivity (ρ = 1.59 µΩ·cm silver, 2.44 gold, at 20 °C, the published pure-metal standings) and the ampacity check states plainly that no NEC ampacity standing exists for them, rather than estimating one.
Definitions — sizes and units. AWG is the American Wire Gauge, the gauge scale for the smaller conductors: as the AWG number falls the conductor grows, from 14 AWG up through 1, 1/0, 2/0, 3/0 and 4/0 AWG. Above 4/0, sizes are stated directly in kcmil — thousands of circular mils. A circular mil is the area of a circle one mil (0.001 inch) in diameter, and a conductor’s circular-mil area is its diameter in mils, squared: the unit in which the K-form of the drop is worked, and the area standing carried for every size in this tool, 250 through 2000 kcmil. Siemens (S), the unit of conductance, is the reciprocal of the ohm. PF is the load power factor, cos φ.
Definitions — system voltage: a standard, not a measurement. The system voltage is chosen, not typed: it is one of the standard voltages the installation is built to, and each choice carries its system standing. 120 V is the single-phase line-to-neutral standing — the leg voltage of the 120/240 V single-phase service and of the 208Y/120 V wye system. 208 V is the three-phase wye line-to-line standing (208Y/120 V). 240 V is the single-phase line-to-line standing (120/240 V) and the three-phase delta line-to-line standing. 277 V is the line-to-neutral standing of the 480Y/277 V wye system. 480 V is the three-phase line-to-line standing (480Y/277 V wye; 480 V delta). 600 V is the three-phase line-to-line standing (600Y/347 V wye; 600 V delta). These are standards, not readings: a voltmeter on a live system reads whatever the moment gives, a few volts either way, but a design stands on the standard the system is built to — so this field presents the standards as choices to tap, with no free entry. The run’s other figures stand the other way: the load current and the one-way distance are measurements of the particular run, as an ammeter and a tape would read them, and those are entered as measured.
Definitions — conduit and raceway types, and what each governs. A conduit choice governs one thing in this tool: which of NEC Table 9’s two reactance classes the run stands in — the magnetic steel class or the nonmagnetic class — and with it the Table 9 AC resistance standing, which the table also prints by raceway. EMT, electrical metallic tubing, is the thin-wall steel tubing of Article 358; steel class. RMC, rigid metal conduit, is the heavy-wall threaded steel raceway of Article 344; steel class. IMC, intermediate metal conduit, is the lighter-wall threaded steel raceway of Article 342; steel class. FMC, flexible metal conduit, is the flexible steel raceway of Article 348; steel class. LFMC, liquidtight flexible metal conduit, is the Article 350 flexible steel raceway with a liquidtight polymer jacket; steel class. Rigid aluminum conduit is the Article 344 rigid raceway in aluminum, a nonmagnetic metal: Table 9 prints its reactance with the PVC standing, so it carries the nonmagnetic class. PVC is polyvinyl chloride, the rigid nonmetallic conduit of Article 352 — Schedule 40 at the standard wall, Schedule 80 at the heavier wall where physical protection is required; the wall changes the conduit, not the magnetic standing, so both carry the nonmagnetic class. ENT, electrical nonmetallic tubing, is the pliable corrugated nonmetallic raceway of Article 362; nonmagnetic class. Cable assembly — no raceway is the standing for conductors run as a cable (such as NM-B or MC cable) rather than in a conduit: Table 9 publishes conduit standings only, so this option carries the nonmagnetic class figure as the nearest published geometric standing, and every result names it as such. The raceway materials themselves: steel is magnetic, and its class stands higher in reactance because the steel concentrates the magnetic field around the conductors; aluminum is a nonmagnetic metal; PVC is a nonmagnetic polymer. That one magnetic difference is the whole of what the conduit governs here.
Definitions — insulation types, and what each governs. An insulation choice governs the ampacity constraint: the Table 310.15(B)(16) column the conductor answers to, which is the type’s temperature rating at the location standing (dry or wet) chosen beside it. The type letters are the Code’s own letter system (NEC Table 310.4(A)): T = thermoplastic insulation; H = heat-resistant, a 75 °C rating; HH = high heat, a 90 °C rating; W = suitable for wet locations; N = a nylon jacket over the insulation; X = cross-linked polymer insulation; R = rubber insulation; U = underground use; and a -2 suffix raises the type to a 90 °C standing in wet locations as well as dry. By type: THHN — thermoplastic, high heat (90 °C), nylon jacket; a dry and damp location type, carrying no wet standing of its own. THWN — thermoplastic, heat-resistant, wet-rated, nylon jacket: 75 °C in dry and wet locations. THWN-2 — the -2 form: 90 °C in dry and wet locations. THHN/THWN-2 is the dual-rated conductor as manufacturers supply it, marked with both types: 90 °C dry under THHN, 90 °C wet under THWN-2. THW — thermoplastic, heat- and moisture-resistant: 75 °C, dry and wet. TW — thermoplastic, moisture-resistant: 60 °C, dry and wet, the oldest of these standings. XHHW — cross-linked polymer, high heat, wet-rated: 90 °C dry, 75 °C wet. XHHW-2 — the -2 form: 90 °C in dry and wet locations. RHW — rubber, heat- and moisture-resistant: 75 °C, dry and wet. RHW-2 — the -2 form: 90 °C in dry and wet locations. USE — underground service entrance: a 75 °C type whose seat is underground and wet service work. USE-2 — the -2 form: 90 °C, dry and wet. UF-B — underground feeder and branch-circuit cable: its conductors are 90 °C rated, but NEC 340.80 sets its ampacity at that of 60 °C conductors, and the rule is printed beside its results. NM-B (Romex) — nonmetallic-sheathed cable, the Article 334 cable of dry locations: its conductors are 90 °C rated, but NEC 334.80 stands its ampacity on the 60 °C basis, and that rule is printed in words beside every NM-B result, never applied silently. Romex is Southwire’s trademark for this cable; NM-B is the NEC type designation — both standings of the name stand. Where a type carries no standing at the location chosen (THHN or NM-B at a wet location), the ampacity check says so in words and returns no figure.
Definitions — conductor materials. Copper is the defining conductor material of the NEC tables (100% IACS, the conductivity standard itself) and aluminum the lighter, larger-for-the-same- ampacity standing beside it (about 61% IACS): both stand on the Code’s tables at every size in this tool. Silver is the most conductive metal (about 106–108% IACS) and gold a corrosion-proof conductor of about 70% IACS; both stand here for laboratory and specialized cases, computed from resistivity because the NEC tables carry no standings for them, as stated above. What a material governs here is the resistance (through its table standing or its resistivity and temperature coefficient), the conductance returned beside it, and whether an ampacity standing exists to check at all.