The correction that stops the supply carrying reactive power.
Power factor is the ratio of real power to apparent power — PF = kW ÷ kVA = cos φ, the cosine of the angle between them. The reactive power the load draws is kVAR = kW × tan φ. A capacitor bank supplies that reactive power locally, at the load, so the supply no longer carries it: the correction is the difference of the two reactive figures, kW × (tan φ₁ − tan φ₂). The real power does not change — the load does the same work — but the apparent power falls, which frees capacity in the transformer and the conductors feeding the load, and reduces the losses their current causes. Many tariffs bill demand on kVA or penalize a low power factor; the tariff’s own terms govern that side of the figure.