Harmonics

Distortion, true RMS current, and the K-factor.

amperes
% of fund.
% of fund.
% of fund.
% of fund.
% of fund.
% of fund.
—

A harmonic is a current at a whole-number multiple of the fundamental frequency — the 3rd at 180 Hz on a 60 Hz system, the 5th at 300 Hz, and so on. Total harmonic distortion here is measured against the fundamental, the convention IEEE 519 uses: THD = √(Σ Iₕ²) ÷ I₁. (The other convention, against the total RMS current, reads lower and is not the one used here.) The total RMS current is what actually heats conductors and transformers, and it is always at least the fundamental. The triplen harmonics — 3rd, 9th, and their kin — do not cancel in the neutral of a three-phase four-wire system; they add there, which is why neutrals in harmonic-rich buildings are sized for them. The K-factor weights each component by the square of its order, because eddy-current heating in a transformer rises with frequency squared; a transformer feeding this load is chosen by its K rating.